| Product – Code | Nominal Cross Sectional Area |
Max. Conductor Resistance | Operating Capacitance |
Inductance | Thickness of Conductor Screen |
Thickness of Insulation |
Thickness of Insulation Screen |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Weight |
|||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| DC at 20 °C | AC at 90 °C | ||||||||||||
| mm² | Ω/km | Ω/km | Ω/km | µF/km | mH/km | mH/km | mm | mm | mm | mm | mm | kg/km | |
| G-PH-CG20-XD-01-BH | 240 R | 0.0754 | 0.0970 | 0.0972 | 0.1420 | 0.6573 | 0.4725 | 1.2 | 18.0 | 1.2 | 4.5 | 74.6 | 6585 |
| G-PH-CG21-XD-01-BH | 300 R | 0.0601 | 0.0777 | 0.1512 | 0.1512 | 0.6404 | 0.4556 | 1.2 | 18.0 | 1.2 | 4.5 | 76.8 | 7310 |
| G-PH-CG22-XD-01-BH | 400 R | 0.0470 | 0.0613 | 0.0617 | 0.1623 | 0.6212 | 0.4364 | 1.2 | 18.0 | 1.2 | 4.5 | 79.5 | 8295 |
| G-PH-CG23-XD-01-BH | 500 R | 0.0366 | 0.0485 | 0.0491 | 0.1757 | 0.6027 | 0.4179 | 1.2 | 18.0 | 1.2 | 4.5 | 82.8 | 9555 |
| G-PH-CG24-XD-01-BH | 630 R | 0.0283 | 0.0384 | 0.0932 | 0.1903 | 0.5858 | 0.4009 | 1.2 | 18.0 | 1.2 | 4.5 | 86.4 | 11045 |
| G-PH-CG25-XD-01-BH | 800 R | 0.0221 | 0.0311 | 0.0322 | 0.2080 | 0.5698 | 0.3850 | 1.2 | 18.0 | 1.2 | 4.5 | 90.8 | 13095 |
| G-PH-CM26-XD-01-BH | 1000 S | 0.0176 | 0.0246 | 0.0249 | 0.2403 | 0.5510 | 0.3661 | 1.5 | 18.0 | 1.2 | 4.5 | 98.9 | 16045 |
| G-PH-CM27-XD-01-BH | 1200 S | 0.0151 | 0.0218 | 0.0222 | 0.2506 | 0.5439 | 0.3590 | 1.5 | 18.0 | 1.2 | 4.5 | 101.5 | 17530 |
Single Core Copper Conductor, XLPE insulated 76/132 (145)
Copper wire screen and HDPE sheath (CU/XLPE/CW/HDPE)
76/132 (145) kV
Stranded circular or segmental compacted copper conductor with swelling powder, semi-conductive water blocking tape, conductor screen, XLPE insulation, non-metallic insulation screen, copper wire metallic screen, non-conductive water blocking tape, copolymer aluminum tape, HDPE sheath with graphite coating or extruded semi-conducting layer.
Suitable for direct burial, installation on trays or in ducts.
Flame retardant PVC sheathed or MDPE, LLDPE Sheathed available upon request. Metallic screen designed for 40 kA / 1 s per three phases as default; other designs available.
The above data is approximate and subject to manufacturing tolerances