| Product – Code | Nominal Cross Sectional Area |
Max. Conductor Resistance | Operating Capacitance |
Inductance | Thickness of Conductor Screen |
Thickness of Insulation |
Thickness of Insulation Screen |
Thickness of Outer Sheath |
Approx. Overall Diameter |
Approx. Weight |
|||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| DC at 20 °C | AC at 90 °C | ||||||||||||
| mm² | Ω/km | Ω/km | Ω/km | µF/km | mH/km | mH/km | mm | mm | mm | mm | mm | kg/km | |
| G-PH-CM26-XF-01-BH | 1000 S | 0.0176 | 0.0246 | 0.0248 | 0.1888 | 0.5799 | 0.3951 | 1.5 | 25.0 | 1.5 | 4.5 | 114.3 | 16045 |
| G-PH-CM27-XF-01-BH | 1200 S | 0.0151 | 0.0218 | 0.0221 | 0.1963 | 0.5721 | 0.3873 | 1.5 | 25.0 | 1.5 | 4.5 | 116.9 | 20295 |
Single Core Copper Conductor, XLPE insulated 127/220 (245)
Copper wire screen and HDPE sheath (CU/XLPE/CW/HDPE)
127/220 (245) kV
Stranded circular or segmental compacted copper conductor with swelling powder, semi-conductive water blocking tape, conductor screen, XLPE insulation, non-metallic insulation screen, copper wire metallic screen, non-conductive water blocking tape, copolymer aluminum tape, HDPE sheath with graphite coating or extruded semi-conducting layer.
Suitable for direct burial, installation on trays or in ducts.
Flame retardant PVC sheathed or MDPE, LLDPE Sheathed available upon request. Metallic screen designed for 63 kA / 1 s per three phases as default; other designs available.
| Product – Code | Nominal Cross Sectional Area |
Laying conditions: Flat formation | ||
|---|---|---|---|---|
| Type of Earthing Bonding System |
Direct burial | in Air (Shaded) | ||
| mm² | ||||
| G-PH-CM26-XF-01-BH | 1000 S | Double End Bonded |
1012.00 | 1545.00 |
| G-PH-CM27-XF-01-BH | 1200 S | 1085.00 | 1672.00 | |
The above data is approximate and subject to manufacturing tolerances